Wire Gauge & Voltage Drop

Size a wire run for acceptable voltage drop — or compute the drop on a given size — across copper, aluminium and other conductor materials, in AWG or metric mm².

Calculation direction

Run and conductor

e.g. 12, 120 or 230 - read in the selected unit.

e.g. 10, 25 or 100 - read in the selected unit.

e.g. 10, 30 or 100 - read in the selected unit.

Resistivity at 20 C: Copper (annealed) uses 1.72e-8 ohm-m - see the limits for the table sources.

Degrees C, e.g. 20, 40 or 60 - leave empty to use the 20 C table value.

e.g. 3, 5 or 10 - read in the selected unit.

The entered length is the ONE-WAY run - the loop resistance doubles it to count the go and return conductors, and every result says so. Units are picked per field; switching a unit reinterprets the same number, it never rewrites it. This is a DC / low-frequency resistance model - reactance and skin effect are out of scope, and code ampacity is a separate check this tool never makes.

Result

Enter the system voltage, load current, one-way run length, conductor material and the max drop you accept (e.g. 5 for 5%). The loop counts both conductors - the entered length is one-way.

Before you rely on this

  • DC / low-frequency approximation: R = rho*L/A ignores reactance, inductance and skin effect. Fine for DC and ordinary 50/60 Hz runs (skin depth in copper is about 9-10 mm at 50 Hz), but long runs near resonance or higher frequencies need a different model.
  • Go + return convention: the loop length is 2 x the one-way run - both conductors count. Some online calculators use only the one-way length and understate the drop by half.
  • Resistivity is at 20 C unless you enter an operating temperature; the adjustment rho_t = rho20*(1+alpha*(T-20)) is a linear approximation - real metals deviate at temperature extremes.
  • Material values are typical handbook resistivities (CRC/IACS family); copper-clad aluminium varies with cladding thickness and alloy, and the nichrome and steel entries are approximate ranges.
  • Code ampacity is a separate check: this tool never claims a code-compliant conductor or breaker size - conductor selection, overcurrent protection and voltage-drop limits defer to wiring code (NEC/CEC/IEC as applicable).
  • AWG sizes are nominal solid-wire cross-sections (4/0 through 30 AWG); stranded constructions have slightly different area and resistance, and runs needing more than 4/0 are reported by mm2 instead.

Enter the system voltage, load current, one-way run length, material and max drop %.

Privacy settings

Checking…

We count anonymous tool use and coarse errors to improve ToolDeck. We do not send your files, pasted text, generated links, or results. Normal network delivery still exposes connection metadata to Cloudflare. Your choice is stored only in this browser's local storage — we do not create a visitor ID. Decline opts out; your browser's Global Privacy Control or Do Not Track signal overrides any choice.