Wire Gauge & Voltage Drop

Size a wire run for acceptable voltage drop — or compute the drop on a given size — across copper, aluminium and other conductor materials, in AWG or metric mm².
Run and conductor
e.g. 12, 120 or 230 - read in the selected unit.
e.g. 10, 25 or 100 - read in the selected unit.
e.g. 10, 30 or 100 - read in the selected unit.
Resistivity at 20 C: Copper (annealed) uses 1.72e-8 ohm-m - see the limits for the table sources.
Degrees C, e.g. 20, 40 or 60 - leave empty to use the 20 C table value.
e.g. 3, 5 or 10 - read in the selected unit.
The entered length is the ONE-WAY run - the loop resistance doubles it to count the go and return conductors, and every result says so. Units are picked per field; switching a unit reinterprets the same number, it never rewrites it. This is a DC / low-frequency resistance model - reactance and skin effect are out of scope, and code ampacity is a separate check this tool never makes.
Result
Enter the system voltage, load current, one-way run length, conductor material and the max drop you accept (e.g. 5 for 5%). The loop counts both conductors - the entered length is one-way.
Before you rely on this
- DC / low-frequency approximation: R = rho*L/A ignores reactance, inductance and skin effect. Fine for DC and ordinary 50/60 Hz runs (skin depth in copper is about 9-10 mm at 50 Hz), but long runs near resonance or higher frequencies need a different model.
- Go + return convention: the loop length is 2 x the one-way run - both conductors count. Some online calculators use only the one-way length and understate the drop by half.
- Resistivity is at 20 C unless you enter an operating temperature; the adjustment rho_t = rho20*(1+alpha*(T-20)) is a linear approximation - real metals deviate at temperature extremes.
- Material values are typical handbook resistivities (CRC/IACS family); copper-clad aluminium varies with cladding thickness and alloy, and the nichrome and steel entries are approximate ranges.
- Code ampacity is a separate check: this tool never claims a code-compliant conductor or breaker size - conductor selection, overcurrent protection and voltage-drop limits defer to wiring code (NEC/CEC/IEC as applicable).
- AWG sizes are nominal solid-wire cross-sections (4/0 through 30 AWG); stranded constructions have slightly different area and resistance, and runs needing more than 4/0 are reported by mm2 instead.
Enter the system voltage, load current, one-way run length, material and max drop %.